LuGao proudly leads as a dedicated outdoor vacuum circuit breaker manufacturer, introducing the Outdoor Column High Voltage Electric Vacuum Circuit Breaker—an exemplary innovation.This multifunctional intelligent device seamlessly integrates the capabilities of a vacuum breaker, vacuum load switch, recloser, and sectionalizer—four essential switches in one.The primary configuration comprises a vacuum breaker, CH-40 controller, and an external voltage transformer.Notably, in bilateral PT, a distribution automation line ring network is available, offering enhanced flexibility and functionality.Choose LuGao for groundbreaking solutions that redefine the benchmarks of outdoor vacuum circuit breakers, bringing together versatility and intelligence in a single device.
Lugao is a outdoor vacuum circuit breaker supplier.Our outdoor vacuum circuit breaker are widely used in the 10kV, 13kV city, rural power grid space ring network for disconnecting switches, contact switches, and automatic switch devices, which can implement the ring deployment line load. It can be used as a boundary switch (commonly known as watchdog) in the branch line of power supply, used as reclosers and sectionalizers in feed overhead distribution networks. The outdoor vacuum circuit breaker comes with remote management patterns, protection and control functions, and communication capabilities. It provides reliable detection and judgment, mA-level zero sequence current sensing, and short-circuit current between phases, realizing the automatic removal of single-phase grounding faults and phase-to-phase short-circuit faults. The main switch is a vacuum arc, and the insulation adopts SF6, N2 mixed gas. The case introduces Japan, Germany, French gas sealing, explosion-proof, insulation system technology, ensuring overall excellent sealing performance. Inside, it is filled with SF6, N2 mixed gas, which does not leak and is not affected by the external environment. The spring operating mechanism, with miniaturization and performance optimization design, enhances action reliability well beyond traditional spring mechanisms.
1. Ambient air temperature: -5~+40 and the average temperature should not exceed +35 in 24h.
2. Install and use indoors. Altitude above sea level for operation site should not exceed 2000M.
3. Relative humidity should not exceed 50% at max temperature +40. Higher relative humidity is allowed at lower temperature. Ex. 90% at +20. But in view of the temperature change, it is possible that moderate dews will produce casually.
4. Installation gradient not exceed 5.
5. Install in the places without fierce vibration and shock and the sites insufficient to erode the electrical components.
6. Any specific requirement, consult with manufactory.
Comprehensive set of type tests ensure the breaker's reliability and compliance.
Constructed with hydrophobic epoxy resin, ensuring safety and environmental friendliness.
Equipped with a high-reliability vacuum interrupter for efficient performance.
Features a manual or electric spring operating mechanism, ensuring long electrical and mechanical life.
Incorporates electronic current/voltage transformers with high accuracy for precise measurements.
Utilizes digital signal transmission with anti-jamming capabilities for reliable communication.
Versatile functionality, capable of serving as a recloser and segmenter.
Offers three-stage current protection and supports multiple feeder automation modes.
Boasts strong sealing, ensuring reliable operation in diverse environmental conditions such as humidity, high cold, high dry heat, and high pollution.
Complies with E2, M2, C2 standards for outdoor vacuum circuit breakers, ensuring high-quality performance.
Electric Parameter | ||
Model | ZW20-12F、ZW20-12、ZW20-12G | |
Parameter | Unit | Value |
Rated voltage | kV | 12 |
Rated frequency | Hz | 50 |
Rated current | A | 630、1000、1250 |
Rated short-circuit breaking current | kA | 20、25 |
Rated peak withstand current (peak) | kA | 50、 63 |
Rated short-time withstand current (4s) | kA | 20、25 |
Rated short-circuit making current (peak value) | kA | 50、63 |
Mechanical life | times | 10000 |
Rated current breaking times | times | 10000 |
Rated short-circuit breaking current breaking times | times | 30 |
Main Mechanical Parameters | ||
Parameter | Unit | Value |
Power frequency withstand voltage (1min): phase-to-phase, ground/fracture | kV | 42/48 |
Lightning impulse withstand voltage (peak value) phase-to-phase, ground/fracture | kV | 75/85 |
Secondary circuit 1min power frequency withstand voltage | kV | 2 |
Net weight | kg | ≤140(with disconnector ≤170) |
Contact Spacing | mm | 9±0.5 |
Victory Overtravel | mm | 3±0.5 |
Opening speed | m/s | 1.2+0.2 |
closing speed | m/s | 0.6±0.2 |
Contact closing bounce time | ms | ≤2 |
Phase center distance | mm | 135±1.5 |
External live air insulation distance | mm | 240±2 |
External creepage ratio | cm/kV | 3.8 |
≤2 | ||
Three-phase opening is not periodic | ms | ≤2 |
Conductive circuit resistance of each phase | Q | ≤150(with disconnector ≤200) |
Closing time | ms | ≤45 |
Opening time | ms | ≤45 |
Isolation fracture distance | mm | ≥190 |
The contact knife just-close position is skewed | mm | ≤2 |
Manual opening and closing operating torque | N.m | ≤150 |
Rated power of energy storage motor | w | > 40 |
Rated voltage of energy storage motor | V | AC220 |
Rated closing operating voltage | V | AC220 |
Maximum/minimum closing operating voltage | V | AC264/143 |
Rated opening operating voltage | V | AC220 |
Maximum/minimum opening operating voltage | V | AC264/143 |
Maximum/minimum motor voltage | V | AC242/187 |
SF6 gas rated pressure (gauge pressure) | MPa | “0” |