Lugao is a 220KV Current Transformer Electric Substation Equipment manufacturer with 15 years of professional experience. As a China Famous Trademark, our products exemplify quality. Our voltage transformer earned global acclaim, exported to over 30 countries and regions, showcasing our commitment to excellence.
Lugao is a 220KV Current Transformer Electric Substation Equipment Suppliers with 15 years of professional experience
Lugao recognized as a Famous Trademark of China.
Our 220/230kV CT has been successfully deployed in Pakistan, Mongolia, Bangladesh, Syria, North Korea, Chile, Peru, and within China State Grid without any quality issues. We offer two design options:
Type One: Live tank with secondary windings at the top
Type Two: Dead tank with secondary windings at the bottom,
Both designs boast proven techniques, operating for decades. A hermetically sealed stainless steel metallic bellows at the top protects voltage transformer oil from moisture, extending its lifespan. An oil level gauge on the bellows facilitates monitoring oil volume changes. The base options include spray painting, hot galvanizing, or cast aluminum, providing high corrosion resistance. Choose Lugao for reliable, innovative solutions in the power industry.
Installation elevation does not exceed 2000 meters
Ambient temperature: -5°C-40°C; The average temperature is not higher than +35°C
The installation site should be dry and ventilated; The relative humidity of the air is not greater than 80%, and there is no aggressive explosive media around
It is oil/paper insulation structure. The main insulation is wound by high voltagecable paper, and is placed several capacitor screen of voltage division in the primaryinsulation,which can improve electric field distributing and decrease theconsumption of insulation material, immersed with voltage transformer oil after desiccatingunder vacuum. It has advantages of stable and reliable performance of insulation. rich operated experience, long service time. Perfect fluidity performance of voltage transformer oil is good for heat dissipation, it alsohas self recover ability for the failure of partial discharge caused by air bubble
and dust.
Hermetically sealed stainless steel metallic bellows is installed on the top, whichprotect the voltage transformer oil from moisture and extend the life time. also there is a oillevel gauge on the bellows for observing the changing of oil volume. There is a multi function oil drain valve on the base, which make it more convenientfor oil sampling, drainingThe current ratio can be adjusted easily by changing the connecting plate to seriesor parallel connection.
All adopted insulation parts are environmental protection materialsSecondary terminal board is made of epoxy casting, the sealing performance ismore reliable.
The base uses spray painting or hot galvanizing, which gives a high degree ofcorrosion resistance.
Fasteners and nameplate are stainless steel
Product Name | 220kv current transformer 220kv electric substation equipment |
Origin | Dalian,China |
Phase | Single |
Coil Structure | Wound |
Color | Brown/Grey |
Frequency | 50/60Hz |
Certification | ASTA/CTQC/IEC/SGS/ISO9001 |
Package | Wooden Carton |
Delivery Time: | 30 days |
Rated voltage, kV | 66/69 | 110/115 | 132/138 | 220/230 |
Highest voltage for equipment, kV | 72.5 | 126/123 | 145 | 245/252 |
Rated frequency, Hz | 50; 60 | |||
Rated power frequency withstand voltage, kV | 140/160 | 230 | 275 | 460 |
Rated lightning impulse voltage, kV | 325/350 | 550 | 650 | 1050 |
Flashover distance, mm | 700 | 1100 | 1300 | 2100 |
Cree. distance, mm | W1:1450 | 2520 | 2900 | 5040 |
W2:1820 | 3150 | 3630 | 6300 | |
W3:2250 | 3910 | 4500 | 7820 | |
Mechanical load, N | 3000 | 3000 | 4000 | 4000 |
Rated primary current, A | 1~4000 | |||
Rated secondary current, A | 1;2;5 | |||
Accuracy class | 0.1; 0.2; 0.5; 0.2S; 0.5S; 0.5S; 5P; 10P; PX;TPX;TPY… | |||
Rated output(recommended value), VA | 1A: 10~50 VA | |||
2A: 10~50 VA | ||||
5A: 15~50VA | ||||
Instrument security factor FS | 5; 10 | |||
Accuracy limit factors ALF | 10; 15; 20; 25; 30; 40 | |||
Short-time thermal current (Maximum), kA | 40kA/3s |